Fault Loop Impedance Calculation -
The most common formula used by electricians to determine the total impedance at the furthest point of a circuit is:
If your calculation shows $Z_s$ is too high, but your cable run is short, the problem lies with the supply ($Z_e$). fault loop impedance calculation
To ensure a compliant installation:
For a 6A Type B breaker, the maximum ( Z_s ) is typically around 7.66 ohms (230V / 30A, where 30A = 5 x 6A). Since 1.29 ohms < 7.66 ohms, the design is safe. However, if the circuit were 200 meters long, ( R_1+R_2 ) would rise to 4.7 ohms, making ( Z_s ) over 5 ohms—still below 7.66, but close. If a Type C breaker (10x rated current) were used, ( Z_{s(max)} ) would drop to 3.83 ohms, and the same 200m circuit would fail. The most common formula used by electricians to
(External Impedance): The impedance of the supply side, measured at the intake (the "origin") of the installation. This includes the service cable and the transformer's windings. R1cap R sub 1 However, if the circuit were 200 meters long,
Technical Report: Earth Fault Loop Impedance Calculation 1. Executive Summary Earth fault loop impedance ( Zscap Z sub s
This is safer as it is done with the power off.